Implementation of Inverter Section of Transformerless On-Line UPS

Design and Simulation of a Transformerless On-Line UPS System

by Rajeshbhai Bediya*,

- Published in Journal of Advances in Science and Technology, E-ISSN: 2230-9659

Volume 11, Issue No. 22, May 2016, Pages 0 - 0 (7)

Published by: Ignited Minds Journals


ABSTRACT

This paper tended to the outline of online uninterruptible power supply (UPS) framework with a low recurrence transformer for disengagement, in light of given details which incorporate sidestep switch and battery and considered the focused on open circle operation. Contingent upon the application, the online UPS framework is formed by two phase changes of AC/DC and DC/AC, the nook of these freeloading impacts of all parts and gadgets is imperative to outline the UPS framework for satisfactory execution. The underlying phase of the outline depends on the hypothetical counts and couple of suppositions has been made all through the plan. Reproduction work has been done by MATLAB/Simulink program to approve the operation of the online UPS framework with low recurrence transformer disengagement. The investigation of the outcomes are given and the avocations respects to execution assessment parameters which some are not fulfilled the plan particulars are talked about in subtle elements

KEYWORD

inverter section, transformerless, online uninterruptible power supply, low frequency transformer, bypass switch, battery, open loop operation, AC/DC conversion, DC/AC conversion, simulation

1. INTRODUCTION

The online UPS is regularly connected for situations where electrical disengagement is important or for an exceptionally delicate to power vacillations types of gear. The online UPS commonly costs a great deal more, because of it having a much more prominent current ACto-DC battery-charger/rectifier, and with the rectifier and inverter intended to run constantly with enhanced cooling frameworks "Ref. (Bekiarov and Emadi, 2002)". The online power supply gets its name from the way that the info line power is not associated with the yield amid typical operation. Rather, the information control first experiences an AC to DC converter where the DC voltage is utilized to charge the UPS' principle battery. The battery then, thus, is releasing through a DC to AC inverter and steered through an exchange switch for the yield voltage. This procedure can be alluded to as a twofold transformation of the information control "Ref. (Jae-Kyu Park, Jung-Min Kwon, 2008).".The significant preferred standpoint of online UPS is the aggregate detachment between the info line voltage and the yield voltage. Another favorable position is its exchanging time when the information line control comes up short. For this situation, the exchanging time is non-existent. The main part that falls flat amid the blackout is the charger for the battery. By and large the Uninterruptible power frameworks (UPS) gives add up to freedom amongst information and yield voltage adequacy and recurrence, and, along these lines, high yield voltage quality can be acquired "Ref. (Rathmann and Warner, 1996) ". This permit there to be zero interference when a power disappointment happens, a burden to the online UPS is the expansive measure of force expended brought about by the twofold transformation handle. This power utilization brought about warmth misfortune and extraordinarily influences the framework's productivity. The twofold transformation additionally needs to happen continually "Ref. (Nie, et. al., 2003. Wders, et. al., 1994)". Along these lines, the dependability of parts used to make the charger; rectifier, inverter and the kind of battery utilized must be of a higher quality. This expanded the cost of these sorts of units up high contrasted with the lower quality move down UPS. Fig. 1 is a streamlined square outline of the online UPS with low recurrence disengaging transformer. "Ref. (Hirao, et. al., 1998)"

Fig. (1) Block Diagram of Typical On-line UPS with Low Frequency Isolating Transformer

Low recurrence transformer disconnection in online UPS is one of the real sorts of twofold transformation topologies. This topology ordinarily connected a secluding transformer at yield and the framework works at low recurrence. The measure of transformer is commonly bigger and utilized as a part of high power evaluations. However the exchanging recurrence is restricted up to 2 kHz as it were. The disservice of this topology is that it delivers high acoustic commotion from transformer and channel reactor and have poor transient reaction to changes in load and information voltage "Ref. (Chiang, et. al., 2000)". In this paper, the on-line UPS framework in open-circle operation with a low recurrence transformer is planned and execution because of its waveform of operations is assessed. The outcomes at the yield of each UPS stage are watched. The general plan strategy all through the culmination of this paper is appeared in Fig. 2.

Fig. (2) Flowchart of the Methodology for the design of UPS system.

The premise of on-line UPS frameworks inunderstanding its operation, the low recurrence transformer in the UPS and also choice of the battery are considered all through this task. In addition, the decisions of ideal estimations of capacitive and inductive components in the general UPS framework are likewise taken into records. Additionally examine specific end goal to comprehend the idea of reenactment process.

1.1 Design calculations and consideration

The topology of the on-line UPS framework configuration is appeared in Fig. 3. It comprises of an AC/DC rectifier charger at the front-end, a full scaffold DC/AC inverter at the back-end, a battery charger/discharger, battery bank, and two transformers. Circuit topology, hypothetical count and parameters setup with a few suppositions are depicted.

Fig. (3) Block diagram of the online UPS with low Frequency Transformer Isolation.

The online UPS with low recurrence transformer for separation is composed as appeared in the piece graph in Figure 3. It is intended to work with an info AC voltage of 240 Vrms at recurrence of 50 Hz. The framework likewise incorporates two battery packs of 80 Vdc as reinforcement vitality that outcomes to 160 Vdc amid release.

Fig. (4) On-line UPS system with low-frequency transformer circuit configuration Transformer circuit configuration

Other than applying the fundamental parts for online UPS which are AC to DC rectifier and DC to AC inverter, the proposed circuit likewise incorporates

Rajeshbhai Bediya*

utilized to venture down the AC supply voltage from 240 Vrms to 160 Vpeak before it is changed over to 160 Vdc by utilizing the AC to DC rectifier. The DC voltage is then sustained to the inverter with 0.8 tweak record, which results to 128 crests on the yield side of the inverter. The voltageis at long last ventured up to 339 Vpeak by utilizing a low recurrence transformer at the yield side. The total circuit graph is shown in Fig.4. The UPS requires no controller since it works in open circle. This has diminished the unpredictability in the plan.

2. REVIEW OF LITRATURE:

UPS frameworks are for the most part used to supply clean and proceeds with energy to harsh burdens, for example, restorative gear, PCs, guard frameworks, and so forth. As use of this basic load is expanding, on the off chance that they are intruded on account of force disappointment they may bring about specific mishaps. This issue can be settled by utilizing UPS frameworks. UPS frameworks by and large has taking after components: low change over the long haul from online mode to reinforcement mode, low THD, directed yield voltage, high productivity. S. B. Bekiarov et al. [1] presents Classification, Operation, Dynamics, and Control of uninterruptible power supply. In this paper survey of UPS framework is introduced with respect to its topologies and operation, progression and control. The paper additionally expounds the issues confronted in various sorts of utilization. It likewise gives part of force hardware in current patterns, short portrayal of standard UPS frameworks, their preference and burden, and extent of change. S.Rathmannet al. [3] presents delta transformation standard for online UPS.The creator clarifies about the new era Delta change guideline. This paper demonstrates results of issue related with twofold transformation UPS and reason for it. It likewise gives short data of the traditional twofold transformation UPS. An audit of single transformation UPS and line-intelligent UPS topology and its favorable circumstances is finished. Another topology, delta transformation UPS is comprehended and examined with its points of interest. Z. Nie et al. [4] presents control figure revision and electric disengagement in an on-line ups framework utilizing BIFRED converter, exhibits the outline thought and execution investigation of an on-line, minimal effort, superior single-stage Uninterruptible Power Supply (UPS) framework in view of Boost Integrated Fly-back Rectifier Energy stockpiling DC/DC (BIFRED) converter. The framework comprises of a segregated AC/DC BIFRED converter, a bi-directional DC/DC the contribution from the yield, and effortlessness in control [4]. M.J.Wders et al. [5], For online UPS with wide load extend, gives new BIFRED converter topology. Contribution to yield separation, control figure change and yield voltage direction is shrouded in this BIFRED converter. By utilizing lift and fly-back area in irregular conduction mode the issue of vast capacitor voltage at light load condition is evacuated. The topology demonstrates how this mass capacitor issue is settled amid light load condition. N. Hirao et al. [6]. The three leg UPS framework is displayed. This novel topology has one focus leg which is PWM method worked. The middle leg will work as rectifier leg and inverter leg both. The review is done on this topology. (Jae-Kyu Park, Jung-Min Kwon, 2008). The transformer-less on-line continuous power supply with superior is introduced. The given Uninterrupted power supply topology is comprises of four leg converter, the mix of four leg together structures Inverter, rectifier and battery releasing/charging. The motivation behind rectifier is to control DC-interface voltage and to keep up information control consider close to solidarity. The prerequisite of transformer is wiped out by utilizing battery charging/releasing leg. At the point when information control disappointment happen then battery set supplies control requested by the heap by utilizing battery charging/releasing leg. The controlled and immaculate sinusoidal yield voltage is given by inverter. By utilizing this topology the transformer is disposed of and henceforth size, weight and cost of the framework lessens (Jae-Kyu Park, Jung-Min Kwon, 2008).

3. THEORETICAL DESIGN CALCULATIONS

The preparatory outline for the online UPS framework depends on hypothetical figuring’s. These hypothetical counts are utilized as pointers to assess the execution of the UPS framework. It comprises of two principle stages which confined amongst info and yield by the transformer. • Source In this plan, the source is 240V rms. according to particulars. The rms. esteem must be changed over to top an incentive to be utilized for the computations in MATLAB Simulink. In 21st century static uninterruptable power supply frameworks are regularly utilized. They have wide assortment of uses in low medium and high power like as present day PC, CNC and VMC hardware and material apparatus. UPS is turning out to be more famous in light of the fact that its effectiveness is higher, relatively bring down aggregate consonant contortion and dependable operation. The execution of UPS will corrupt with unbalance and nonlinear load, for higher unwavering quality UPS will cost high. These two are fundamental issue with UPS frameworks. Static UPS are sort under three sorts

Classification of Static UPS

 Double Conversion UPS  Off-line

 Line-interactive

On-line UPS

In On-line UPS there is rectifier segment battery charging/releasing segment, inverter area and sidestep switch, this UPS is otherwise called On-line UPS and Inverter favored UPS. The DC transport is in effect persistently supplies by rectifier. Control rating of gadgets is set in a manner that 100% of load power request can meet. Control rating of battery is set in a manner that it ought to supply control amid reinforcement time. Reinforcement time fluctuates with different applications. A normal on-line UPS piece graph is appeared in Fig. 5. To start with AC in coming line is associated with AC/DC converter or rectifier which will change over AC energy to DC and supply it to inverter and battery. The rating of rectifier outlined in a manner that it must meet full load condition and in the meantime charging power require by battery. The prerequisite of go down time is fluctuates with various load. For instance, medicinal hardware needs longer time reinforcement where as in material machines require less reinforcement time. At that point frame DC interface inverter again changes over DC control into AC control. The rating of inverter outlined in a manner that it must meet 100% of load power in typical condition and in move down time, a static sidestep switch is accommodated undesirable condition connect failing of UPS. For this situation finish framework is by go by static switch for coherence of supply to stack. So as to utilize sidestep switch AC supply and yield of inverter should in stage, and that can be accomplish by utilizing stage bolted circle. In the reason this sort of framework is likewise called as twofold transformation framework. This converter supplies inverter and furthermore charges battery; in this manner it has most noteworthy power rating in this topology which expands cost. At the point when input voltage is not in the scope of predefine voltage restrict inverter and battery will supply energy to stack. The coherence of this mode relies on upon back time or till the voltage goes under the range. There is no exchange time frame typical mode to reinforcement mode and again reinforcement mode to ordinary mode so consistent continuous power supply is conceivable. The disadvantage of this strategy is low power component and high THD at info side.

Figure 5 Line diagram On-line UPS Standby UPS

This standby UPS arrangement is otherwise called line favored UPS or disconnected UPS (Bekiarov and Emadi, 2002). Fig. 1-2 indicates single line graph of standby UPS. A remain by UPS comprises of a static switch, battery bank, AC to DC convertor and DC to AC convertor. To enhance nature of yield voltage a channel is utilized. In ordinary method of operation a static switch is shut so load is specifically provided by AC mains. In typical condition battery is charged through AC/DC convertor. Here AC/DC convertor is evaluated at lower control rating than rectifier and charger in an online UPS. Without supply or AC mains being out of safe working extent the DC/AC convertor come into picture and give energy to stack and again come to standby when power is accessible. Span of exchanging is reliant on turn on time of inverter. Change after some time is for the most part ¼ of the AC mains cycle. Bad marks of the framework are long changeover time, no yield voltage direction, no disengagement of load from AC mains, yet the key point is its straightforward outline which makes it minimal effort and little in size.

Line-interactive UPS

The Line interactive UPS is consisting of battery bank which is connected to a bi-directional converter, a series chock and a static switch. Load can be fed through an optional filter. It can operate either as double conversion UPS or as standby UPS. The series choke in not require when line interactive UPS used as standby UPS.

Rajeshbhai Bediya*

For direction of yield voltage and to enhance stack control figure lion's share line intuitive UPS framework works on the web. Line intelligent UPS encouraged load specifically when AC mains is inside as far as possible. The battery set charged through Figure 6 bi-directional AC/DC converter which is associated in parallel with load.

To control yield voltage or to keep up info control consider close to solidarity it might supply receptive energy to stack (Bekiarov and Emadi, 2002). At the point when AC mains are not accessible the bi-directional converter fills in as inverter and supplies the heap from the arrangement of battery. The static switch connecter in the middle of AC mains and load is killed to keep back sustain from inverter to supply. The advantage of utilizing this framework is its straightforward outline, and subsequently, brings down cost and high unwavering quality of the framework then twofold transformation UPS framework. The productivity is additionally higher in this topology due to single stage transformation procedure and great information current sounds concealment. The downside of line intelligent UPS is yield voltage direction is bad. It is a result of inverter is associated in parallel with load rather than arrangement. This topology does not give successful seclusion between AC mains and load. This drawback can be killed by utilizing transformer at yield side yet this will prompts to expansion in weight, size and cost of UPS framework.

4. IUPS DESCRIPTION:

The principle subject of the IUPS is to give the clean and persistent source and satisfactory energy to the heap independent of the source. It comprises of 4-indistinguishable H-Bridge bidirectional converter/inverter station (Bekiarov, et. al., 2003)-(Hirachi, et. al., 1994). They are named as station H1, H2, H3and H4 converter station. The controlling activity is accomplished by with the assistance of SPWM strategy so as to get the unadulterated sine wave (Uematsu, et. al., 1998). This procedure is described by steady plentifulness beats with various obligation cycle for every period and the width of the beats are adjusted to get inverter yield voltage control and furthermore it will lessens the symphonious esteem. In SPWM strategy a sinusoidal regulating sign is contrasted and an exchanging recurrence triangular the width of the entryway drive for the gadgets can be fluctuated and henceforth yield voltage greatness is likewise differed additionally by changing the recurrence of the tweaking wave the central recurrence at the inverter yield changes. All in all terms, strength is an outflow of a subjective level of mishandle that an online UPS framework can deal with past its 0-to-100 percent appraisals while as yet meeting its accessibility prerequisites (Chiang, et. al., 2000). Both sans transformer and transformer based UPS can give brilliant and comparable element over-burden abilities for stage to nonpartisan or three-stage dynamic load occasions. These units give programmed treatment of impermanent over-burdens and blames on the downstream circulation arrange and can give on-the-fly paralleling with the AC sidestep in support of over-burden and load blame administration. Transformer-based UPSs include the advantage of some level of aloof blame dealing with through inward transformers and channels. Most transformer-based plans utilize circuit breakers at key detach focuses (Input, Output, Bypass and Battery). These circuit breakers give over-current assurance and take into account more prominent blame clearing abilities. Some sans transformer outlines may utilize a contactor and wire blend which can introduce issues amid certain over-burden or blame conditions. In particular, an inverter IGBT can flop short which may bring about the contactor to weld and present a DC current onto the transport alongside this the majority of the contactors will be not able open amid DC blame conditions or high, AC blame current circumstances which could be effortlessly taken care of by an appropriately measured electrical switch. Additionally, in a transformer-based UPS, the DC blame current can't go through a separation transformer. Accordingly, the information feeder or the basic transport can't encounter any DC blame conditions, or falling DC issues.

 Robustness:

As a rule terms, strength is an outflow of a subjective level of manhandle that an UPS framework can deal with past its 0-to-100 percent appraisals while as yet meeting its accessibility necessities. Both sans transformer and transformer-based UPS can give incredible and comparable element over-burden abilities for stage to unbiased or three-stage dynamic load occasions. These units give programmed treatment of transitory over-burdens and blames on the downstream conveyance organize and can give on-the-fly paralleling with the AC sidestep in support of over-burden and load blame administration. Transformer-based UPSs include the advantage of some level of aloof blame dealing with through inward transformers and channels. Most transformer-based plans utilize circuit breakers at key disengage more prominent blame clearing capacities. Some without transformer outlines may utilize a contactor and wire blend which can exhibit issues amid certain over-burden or blame conditions. In particular, an inverter IGBT can bomb short which may bring about the contactor to weld and present a DC current onto the transport alongside this the greater part of the contactors will be not able open amid DC blame conditions or high, AC blame current circumstances which could be effectively taken care of by a legitimately measured electrical switch. Additionally, in a transformer-based UPS, the DC blame current can't go through a disengagement transformer. Thus, the info feeder or the basic transport can't encounter any DC blame conditions, or falling DC shortcomings.

5. ENGINE-GENERATOR INTERFACE:

The information channel on the transformer-based plan is sufficiently huge in kVAR to bring about the information control component to wind up distinctly driving (capacitive) when the UPS is delicately stacked (under 40 percent). This can bring about motor generator (Genset) control issues if not considered amid the enginegenerator/UPS mix plan. The additional kVAR of the channel likewise requires that the motor generator be larger than average when contrasted with the UPS control rating. Hence, most UPS makers offer a choice to naturally kill the main power consider under light loads. The sans transformer plan, with its close solidarity control calculate and low info current bending over the full yield stack extend, evades these attributes and permits an all the more firmly coordinated motor generator to be utilized. The motor generator may even now should be larger than average to some degree to deal with the full basic load in addition to battery energizing. As a side note in regards to framework configuration, make certain to affirm that the DG framework and any power circulation segments, can deal with the basic load control element and AC current bending independently from the UPS. Every once in a while, the UPS will be on sidestep, with the basic load fueled straightforwardly from the utility info source, motor generator or other exchange AC source. UPS Output Considerations The yield transformer in the transformer-based UPS configuration gives adaptability in yield voltage, staging and establishing. The delta-wye transformer can be arranged as a 3-wire delta (three stages in addition to ground) or 4-wire wye (three stages in addition to nonpartisan in addition to ground), 600, 480, 400 or 208 Volt framework yield. The wye accommodates adherence to the National Electric Code independently determined impartial definition. It additionally allows the unbiased to be grounded and a nearby circulation reference set up. Establishing focuses for isolated rectifier AC information and sidesteps AC input sources won't should be firmly coupled, as would be required for without transformer plans. Without transformer UPS configuration is information voltage (Figures 6 and 7). Nonpartisan foundation (i.e., 4-wire wye yield) for conveyance happens more distant downstream in a segregation transformer, regardless of whether remain solitary or inside a Power Distribution Unit (PDU). On the off chance that a yield unbiased is required in a without transformer UPS, a fourth leg is added to the inverter (Figure 8). The made impartial does not have attractive segregation and will be referenced.

CONCLUSION:

This paper proposed an outline of on-line UPS framework with Low recurrence transformer disengagement what's more; it has met the outline criteria given inside certain resistance. The figured qualities were confirmed in MATLAB/Simulink programming for check reason. Keeping in mind the end goal to accomplish quick dynamic reaction, low battery voltage, and craved yield voltage, tuning of the parameters are unavoidable. With the change made in the parameters amid reproduction, the yield voltage was effectively being gotten, with low aggregate symphonious mutilation which is 1.82%. Nonetheless, it ought to be noticed that the composed on-line UPS framework contains high aggregate consonant mutilation of info current because of the utilization of uncontrolled rectifier framework. The circuit topology, operation, and control methodology have been depicted. The commitment of this proposed UPS framework is for clarification and seeing how functions and outlines online uninterruptible power supply. The reenactment comes about confirm and focal points of the proposed UPS framework. Framework reaction will likewise be tried under different load condition and fluctuating info supply condition and framework to show quick element reaction. By using the battery charger/discharger, the general effectiveness of the framework will enhanced, and the size, weight, and cost of the framework can be fundamentally decreased. The inverter is freely worked paying little respect to the line condition, and the UPS exchanges continuous energy to the heap. Equipment of inverter segment of transformer-less online UPS will be actualized and exhaustive outcomes will be gotten. Actualizing of SPWM system in inverter enhances yield waveform. By outlining low-pass channel for inverter a sine wave yield voltage will got.

REFERENCES:

S. B. Bekiarov and A. Emadi (2002). “Uninterruptible power supplies: Classification, operation, dynamics, and control,” Proc. IEEE APEC, vol. 1, pp. 597–604. S. Rathmann and H. A. Warner (1996). “NEW GENERATION UPS TECHNOLOGY, THE

Rajeshbhai Bediya*

Z. Nie, S. B. Bekiarov, and A. Emadi. (2003). “An On-Line UPS System with Power Factor Correction and Electric Isolation Using BIFRED Converter”,IEEE, pp.361-366. M.J. Wders, M.G. Egan, J.M.D. Murphy, S. Daly titled (1994). “A BIFRED Converter with a Wide Load Range”,IEEE, pp. 226-231. N. Hirao, T. Satonaga, T. Uematsu, T. Kohama, T. Ninomiya, M. Shoyama (1998). “Analytical consideration of power loss in three-Arm type Uninterruptible power supply”,IEEE, pp. 1886-1891. T. Uematsu, T. Ikeda, N. Hirao, S. Totsuka, T. Ninomiya, and H. Kawamoto (1998). “A study of the high performance single-phase UPS,” Proc. IEEE PESC, vol. 2, pp. 1872–1878. K. Hirachi, A. Kajiyama, T. Mii, and M. Nakaoka (1996). “Cost-effective bidirectional chopper-based battery link UPS with common input–output bus line and its control scheme,” Proc. IEEE IECON, vol. 3, pp. 1681–1686. B. Bekiarov, A. Nasiri, and A. Emadi. (2003). “A new reduced parts online single-phase UPS system,” Proc. IEEE IECON, vol. 1, pp. 688–693. K. Hirachi, M. Sakane, S. Niwa, and T. Matsui (1994). “Development of UPS using new type of circuits,” Proc. INTELEC, pp. 635–642. C. V. Nayar, M. Ashari, and W. W. L. Keerthipala (2000). “Agrid-interactive photovoltaic uninterruptible powersupply system using battery storage and a backup dieselgenerator,” IEEE Trans. Energy Convers., vol. 15, no.3, pp. 348–353. C. C. Yeh and M. D. Manjrekar (2007). “A reconfigurableuninterruptible power supply system for multiple powerquality applications,” IEEE Trans. Power Electron.,vol. 22, no. 4, pp. 1361–1372. J. H. Choi, J. M. Kwon, J. H. Jung, and B. H. Kwon (2005). “High-performance online UPS using three-leg-typeconverter,” IEEE Trans. Ind. Electron. vol. 52, no. 3,pp. 889–897. J. K. Park, J. M. Kwon, E. H. Kim, and B. H. Kwon (2008). “High-performance transformerless online UPS,” IEEETrans. Ind. Electron., vol. 55, no. 8, pp. 2943–2953. converter withthe energy recovery function,” IEEE Trans. Ind.Electron., vol. 55, no. 8, pp. 3022–3029. S. Paudyal, C. A. Cañizares, and K. Bhattacharya (2011). “Optimal operation of distribution feeders in smart grids,” IEEE Trans. Ind. Electron., vol. 58, no. 10, pp.4495–4503. H. C. Chiang, T. T. Ma, Y. H. Cheng, J. M. Chang, and W. N. Chang (2009). “Design and implementation of a hybrid regenerative power system combining grid-tie and uninterruptible power supply functions,” IET Renew. Power Gener., vol. 4, no. 1, pp. 85–99. S. J. Chiang, T. S. Lee, and J. M. Chang (Sep. 2000). “Design and implementation of a single phase three-arm rectifier inverter,”Proc. Inst. Electr. Eng.-Electr. Power Appl., vol. 147, no. 5, pp. 379–384. Jae-Kyu Park, Jung-Min Kwon (AUGUST 2008). “High-Performance Transformer-less Online UPS”, IEEE Transactions on Industrial Electronics, VOL. 55, NO. 8, pp. 2943-2953.

Corresponding Author Rajeshbhai Bediya*

Research Scholar, OPJS University, Rajasthan

E-Mail – aalamjeetsandhu@gmail.com